Immediate Restarting
When dip < 100 mSec. (Immediate restarting is possible as motor's
slippage will not have increased beyond the point where undesirable inrush currents would occur.)
Delayed Restarting
When dip 0.1 - 4 sec as the restored power supply may be in phase
opposition to the Back EMF generated by the motors.
Restarting will be delayed 1-30 Sec. until the residual Back EMF has sufficiently diminished.
Staggering the restarting of the motors prevents simultaneous restarting of all motors, which
can result in undesirable inrush currents.
No Restarting
When dip > 4 sec. for safety reasons.